Fire fighting sprinkler systems Balmoral M100 and M100-B30 sectional tanks are Loss Prevention Certification Board (LPCB) approved for fire fighting sprinkler systems.
• Sprinkler systems must comply with BS EN 12845:2004
• A type AB air gap is required unless connected to a dedicated water supply
• Internal ladders should be stainless steel. External ladders compliant with BS 5395
• Water level indication is required on sprinkler tanks
• The water in sprinkler tanks tends to be inactive for long periods of time. Immersion heaters or other means of preventing freezing may be required
• In the event of a fire, large quantities of continuous flow are required. If a vortex inhibitor is fitted, the volume of water that can be drawn from the tank is increased without the inclusion of air or a reduction in the flow rate.
There are two main types of vortex inhibitor: positive head and suction lift
----IFB 32 to 10" suction lift
Nominal bore (mm)
X (mm)
Y (mm)
80 (3")
90
140
100 (4")
100
185
150 (6")
120
275
200 (8")
150
365
250 (10")
170
455
----EFB suction lift
Nominal bore (mm)
X (mm)
Y (mm)
80 (3")
160
140
100 (4")
160
185
150 (6")
190
275
200 (8")
220
365
250 (10")
240
455
300 (12")
280
555
----EFB positive suction head ----(Champion fitting close coupled)